1000kVA Oil Transformer/

1000 kVA 15 kV/0.8 kV Oil-Immersed Distribution Transformer for Italy Utility Projects – Ecodesign Tier 2

Model:S20-M-1000/15 class (oil-immersed, hermetically sealed)

Rated Capacity:1000 kVA

Phase:Three-phase

Frequency:50 Hz

Rated High Voltage (HV):15 kV (system voltage; 17.5 kV highest equipment voltage, Um)

HV Tapping Range:±2 × 2.5% off-circuit (±5% or OLTC on request)

Rated Low Voltage (LV):0.8 kV (800 V); 0.4 kV / 0.415 kV optional

Vector Group:Dyn11 (LV neutral brought out and earthed; Yyn0 on request)

  • Product Details
  • FAQs
  • Packing & Delivery

transformers,distributon transformers

Quick Answer

A 1000 kVA 15 kV/0.8 kV oil-immersed transformer for an Italian utility project is a three-phase, EU Ecodesign Tier 2 compliant distribution transformer that steps the 15 kV medium-voltage network down to an 800 V low-voltage bus inside a cabina MT/BT or a dedicated MV/LV substation. Italian connection practice allows transformers up to 1600 kVA on 15 kV feeders at 6% impedance, so 1000 kVA is a standard, freely permittable size. The first line item Italian utilities check is Ecodesign compliance under Regulation (EU) 548/2014 Tier 2 — for a 1000 kVA liquid-immersed unit, no-load loss ≤ 770 W (Ao class) and load loss ≤ 10,500 W (Ck class) — together with CE marking, a Dyn11 vector group and an LV neutral brought out and earthed.

Product Overview

This is a three-phase, 50 Hz oil-immersed distribution transformer rated 1000 kVA, with a primary voltage of 15 kV (17.5 kV equipment class, BIL 95 kV) and a secondary voltage of 0.8 kV. Both HV and LV windings are copper. The active part is sealed inside a corrugated-fin steel tank with no conservator, so the insulating oil never contacts air, never needs sampling, filtration or topping-up, and the unit is genuinely maintenance-free for its 25-year design life. Impedance is 6%, the value Italian connection rules assume for MT/BT transformers.

The 800 V low-voltage side is the point of this rating: at 1000 kVA it halves the LV current to roughly 720 A versus 1440 A at 400 V, which means smaller LV cables, busbars and switchgear — a real cost advantage for battery energy storage PCS, rectifier and DC industrial loads, PV plants and large utility districts. 400 V / 415 V secondaries remain available on request for conventional Italian LV networks.

It is built for Italian utility and infrastructure work: cabine MT/BT operated by local distribution companies, industrial district substations, utility and EPC tenders, and renewable plants connecting to the 15 kV / 20 kV distribution grid. Standard supply includes oil-temperature monitoring with alarm/trip contacts and an RS485/Modbus RTU interface, readable by the site SCADA. Manufactured under ISO 9001, ISO 14001 and ISO 45001, designed and tested to IEC 60076-1/-2/-3/-5/-10 and EN 50588-1 / EN 50629, and CE marked with losses declared per Regulation (EU) 548/2014 Tier 2.

Why Italian Utility Projects Specify Sealed Oil-Immersed

Our recommendation: for outdoor compounds, cabine MT/BT and industrial districts, specify a hermetically sealed oil-immersed transformer. Reserve cast resin dry type for indoor electrical rooms, underground substations and any site where Italian fire regulation (DM 03/08/2015) rules out combustible oil.

Two reasons drive the Italian specification. First, total cost: an oil-immersed unit costs less per kVA and its sealed tank removes every periodic oil-maintenance task. Second, integration: Italian MV/LV practice is a delta HV winding with an earthed LV star point — exactly the Dyn11 group this transformer ships in — and the 1000 kVA rating sits comfortably inside the 1600 kVA ceiling that Italian utilities apply to 15 kV feeders at 6% impedance.

Consideration Sealed Oil-Immersed (this product) Cast Resin Dry Type Italian-Site Impact
Installation Outdoor compound or cabina MT/BT with oil bund Indoor electrical room Fire regulation (DM 03/08/2015) usually decides it
Oil containment Needs bund / spill containment per local practice No oil Outdoor and dedicated substations → oil type
Cost per kVA Lowest Typically 10–15% higher Oil wins capex-sensitive utility tenders
Ecodesign Tier 2 Compliant, losses declared on nameplate Compliant (Table I.2 limits) Both acceptable — Tier 2 is mandatory either way
Maintenance None — sealed, no oil sampling ever None Sealed oil removes a recurring OPEX line
Seismic (NTC 2018) Anchoring design available for zones 1–3 Available Large parts of Italy are in seismic zones
Corrosion C4 / C5-M coating for coastal and industrial sites Available Relevant for coastal Italy and port areas
Noise ≤ 60 dB(A) standard; ≤ 55 dB(A) low-noise build Slightly quieter Urban cabine specify a dB limit

EU Ecodesign Tier 2 and 20-Year Running Cost

A 1000 kVA transformer on a utility network stays energised 24 hours a day, so no-load loss runs 8,760 hours a year even at night load. Under Regulation (EU) 548/2014 Tier 2 — mandatory across the EU since 1 July 2021 — a 1000 kVA liquid-immersed unit must not exceed 770 W no-load loss (Ao class) and 10,500 W load loss (Ck class), and the guaranteed values must be declared on the nameplate. Italian utilities frequently specify below these limits, and so do we:

Design option No-load loss P0 Load loss Pk (75 °C) Annual losses (kWh) 20-year electricity cost
Tier 2 basic classes (Ao / Ck) 770 W 10,500 W ≈ 21,460 kWh ≈ € 77,300
Optimised design (typical offer) 650 W 8,400 W ≈ 17,470 kWh ≈ € 62,900
Saving over 20 years — — ≈ 3,990 kWh / year ≈ € 14,400

Key Features

  • EU Ecodesign Tier 2 compliant — guaranteed losses 650 W / 8,400 W, declared on the nameplate per Reg. (EU) 548/2014; low-loss step-lap core in grain-oriented steel.
  • Hermetically sealed corrugated tank — no conservator, no oil sampling, filtration or topping-up for the full 25-year design life.
  • 800 V LV, half the current — ≈720 A per phase at 1000 kVA vs ≈1440 A at 400 V, so smaller LV cables, busbars and switchgear for BESS PCS, rectifiers and PV. 400/415 V on request.
  • Copper HV and LV windings, Dyn11 with earthed LV neutral — the standard Italian MT/BT configuration, with lower losses and better short-circuit withstand (type-tested to IEC 60076-5).
  • Built for the Italian site — seismic design to NTC 2018, C4/C5-M anti-corrosion coating, IP54 cable boxes, fluororubber sealing from -25 °C to +55 °C, ≤60 dB(A) at 1 m.
  • Smart- and environment-ready — oil temperature alarm/trip contacts and RS485/Modbus RTU as standard, 4G/LoRa optional; mineral oil to IEC 60296 or biodegradable natural ester for protected areas.

Typical Applications

  • MV/LV prefabricated substations (cabine MT/BT) and utility substations on 15 kV / 20 kV feeders
  • PV plants and BESS connecting to the Italian MV grid
  • Industrial plants with DC, rectifier or electrolysis loads
  • Infrastructure — rail, metro, airports and ports; YBW compact substation packages with 15/24 kV RMUs

Standards and Certifications

Designed and tested in accordance with IEC 60076-1 (general), IEC 60076-2 (temperature rise), IEC 60076-3 (insulation levels and dielectric tests), IEC 60076-5 (short-circuit withstand) and IEC 60076-10 (sound level), plus EN 50588-1 and EN 50629 for European distribution transformers. Energy performance complies with Regulation (EU) 548/2014 Tier 2, with guaranteed losses declared on the nameplate. CE marked, with the EU Declaration of Conformity issued with every unit; an EU authorised responsible person under Regulation (EU) 2023/988 (GPSR) can be arranged. Connection aspects follow the Italian framework (CEI 0-16 and the CEI 14 series) — Dyn11 vector group, 6% impedance and earthed LV neutral are supplied as standard. Manufactured under ISO 9001, ISO 14001 and ISO 45001. Third-party type test reports (CNAS-accredited laboratory, KEMA or equivalent) available on request. Harmonic duty designed with reference to IEEE C57.110.

Q1: What are the EU Tier 2 loss limits for a 1000 kVA transformer?

A: Under Regulation (EU) 548/2014 Tier 2, mandatory since 1 July 2021, a 1000 kVA liquid-immersed distribution transformer with one winding ≤ 24 kV and the other ≤ 1.1 kV must not exceed 770 W no-load loss (Ao class) and 10,500 W load loss (Ck class); correction factors apply for other voltage combinations. The guaranteed values must be declared on the nameplate. Our standard design guarantees 650 W / 8,400 W — comfortably inside Tier 2 and inside the tighter values Italian utilities often specify.

Q2: Can a 1000 kVA transformer be connected to a 15 kV network in Italy?

A: Yes. Italian utility connection practice (reflected in CEI 0-16) allows MT/BT transformers up to 1600 kVA on 15 kV feeders — and up to 2000 kVA on 20 kV feeders — at 6% impedance, with limits on how many units may be energised simultaneously. A single 1000 kVA unit is therefore a standard, freely permittable size; larger ratings or parallel operation simply need an agreement with the local distribution company.

Q3: What vector group do Italian distribution utilities require?

A: Dyn11 is the de-facto standard. The delta HV winding gives zero-sequence and 3rd-order harmonics a circulating path inside the transformer, and the LV star winding provides the neutral that Italian practice requires to be brought out and earthed. This transformer ships Dyn11 as standard with the LV neutral accessible; other groups are available on request.

Q4: Why specify 800 V low voltage instead of 400 V?

A: Current. At 1000 kVA, an 800 V secondary carries roughly 720 A per phase versus 1440 A at 400 V — half the current, so LV cables, busbars and switchgear can be one or two sizes smaller, which matters in BESS, rectifier and DC industrial installations. Conventional Italian LV networks at 400/230 V are equally supported: 0.4 kV and 0.415 kV secondaries are available at order.

Q5: Does the transformer need seismic qualification in Italy?

A: In seismic zones 1–3, which cover a large part of Italy, yes in practice. Anchoring and structural design to NTC 2018 (the Italian building code, aligned with Eurocode 8) is what procurement asks for. We supply anchoring calculations and design documentation on request, and the tank, radiators and bushings are selected to survive the corresponding seismic acceleration.

Q6: What documents come with CE marking for a transformer?

A: Each unit ships with the EU Declaration of Conformity referencing IEC 60076 / EN 50588-1, routine test reports (winding resistance, ratio and vector group, no-load and load loss, impedance, applied and induced voltage, insulation resistance), the Ecodesign loss declaration per Regulation (EU) 548/2014, and operating instructions. Under Regulation (EU) 2023/988 (GPSR) an EU authorised responsible person can be arranged for importers who need one. Type test reports from a CNAS-accredited laboratory are available on request.

Q7: Which insulating oil should be used in environmentally sensitive areas?

A: Where the substation sits in a water-protection zone, park or environmentally constrained Italian site, specify natural ester instead of mineral oil. Ester fluid is biodegradable, has a much higher fire point (K-class fluid) and allows a smaller oil containment. The transformer can be factory-filled with natural ester to IEC 62776-equivalent specifications; tell us at order stage, because ester affects gasket and paint selection.

Q8: What oil containment is required for outdoor installations?

A: Italian practice requires oil spill containment (a bund or catch pit sized for the oil volume plus fire-quenching aggregate) for oil-filled transformers, per the local fire authority interpretation of DM 03/08/2015. We can supply a matching steel bund frame or advise the pit dimensions from the transformer oil mass, so the civil works are designed correctly the first time.

Q9: How long is the delivery time for a 1000 kVA transformer to Italy?

A: Production is typically 6–10 weeks depending on specification, loss class and order quantity — well below the long lead times European suppliers quote in the current transformer shortage. Shipping is by sea to Genoa, La Spezia, Ravenna or Naples, oil-filled and sealed or drained with oil in drums where regulations require; sea-worthily crated with shock and tilt indicators.

Q10: Is a hermetically sealed oil transformer really maintenance-free?

A: For the oil, yes. A sealed corrugated-fin tank has no conservator, so the oil never breathes air and does not absorb moisture or oxidise. There is no periodic oil sampling, testing, filtration or topping-up for the 25-year design life. What still needs an occasional look are the external items: bushings, cable terminations, gasket faces and the pressure relief valve — a visual inspection once or twice a year is enough.

Shipped oil-filled and factory-sealed (or drained with oil in sealed drums where destination regulations require) on a steel-reinforced wooden pallet, wrapped in moisture-barrier film with desiccant, HV and LV bushings plus cable boxes protected by plywood guards, fitted with lifting lugs and shock/tilt indicators. Suitable for sea freight to Italian ports (Genoa, La Spezia, Ravenna, Naples) and inland road transport; full export plywood crate available on request. ISPM-15 fumigation-free pallets as standard. Final gross weight, crate dimensions and packing list confirmed before shipment.