Smart HV/LV Switchgear/

HXGN17-12 AC metal ring main switchgear (load switch)

  • Product Details
  • FAQs
  • Packing & Delivery

Overview

The HXGN17-12 AC Metal Ring Main Unit switchgear (Load switch) (abbreviated as Ring Main Unit) is a new type of high-voltage switchgeardeveloped to meet the needs of urban power grid renovation and construction.In power supply systems,it is also used for interrupting load curentsand short-circuit curents, as well as closing short-circuit currents. This ring main unit is equipped with FZRN25 and FZRN21 vacuum load switcheswith a spring-operated mechanism that can be manualy or electrically operated, Grounding switches and isolating knives are equipped with manuaoperating mechanisms, This ring main unit features strong system integration, compact size, no risk of combustion or explosion, and reliable “five.prevention” functions.

This ring main unit complies with the relevant provisions of GB3906 “3-35kV Ac Metal-Enclosed Switchgear” and lEc60420 “High-voltage AC LoadSwitch-Fuse Combination Units” standards.

Model Meaning

Terms of Use

▪ Ambient air temperature: -15’C to +40’C

▪ Altitude: 1,000 meters or below;

▪ Humidity conditions: Daly average humidity not exceeding 95%, with daily average water vapor pressure not exceeding 2.2 kPa; monthly averagehumidity not exceeding 90%, with monthly average water vapor pressure not exceeding 1.8 kPa;

▪ Earthquake intensity: Not exceeding magnitude 8;

▪ Locations free from corrosive or flammable gases and other significant pollutants.

Note: lf conditions exceed the above normal operating conditions, users may consult with our company.

Main technical parameters

Item Unit FKN12-12 FZN25-12
Rated voltage 12
1min power frequency withstand voltage kV To the ground and phase 42; lsolation fracture 48
Lightning impulse voltage To the ground and phase 75; Isolation fracture 85
Rated frequency Hz 50
Rated current of main bus 630
Load switch Rated current A 630
Current life at rated current 次time Notless than100
Disconnect no-load transformer capacity kVA 1250
Rated heat stable current kA/s Ground switch 20/2
Rated dynamic stable current(peak) 50
Rated short circuit closing current(peak) kA 50
Rated current of the fuse kA 100
Rated transfer current kA 1500 2000
Rated short-circuit breaking current 315
Fitted with fusemodel S□LAJ-12(XRNT□-10)
Mechanical life time 2000 10000
Auxiliary circuit 1min power frequency voltage kV 2
Operating voltage of electric actuator V Ac DC 220;110
Class of protection IP2X
Overall dimensions (w×d×h) mm 650(850)×900×2000(2200)