Ordinary oil-immersed transformers always contain oil, specifically a special insulating mineral oil (commonly known as transformer oil). Oil-immersed transformers with strict requirements for fire safety, environmental protection, or high overload capacity may use bio-based oil. The oil level in the tank is typically kept between 1/4 and 3/4 of the tank level gauge. During operation, the transformer oil plays a crucial role in insulation, heat dissipation, and arc suppression.
- What kind of oil is typically used in an oil-immersed transformer ?
Ordinary oil-fired transformers use insulating mineral oil (referred to as “transformer oil” in national standards), which is mainly divided into two types: naphthenic and paraffinic. In engineering, the type is usually selected based on the pour point (cold resistance) .
- Transformer oil No. 10 : Pour point not higher than -10℃, suitable for warm regions in Southeast Asia or indoor use.
- Transformer oil No. 25 : Pour point not higher than -25℃. This is the most common type and is suitable for most mild and moderately cold regions.
- Transformer oil No. 45 : Pour point not higher than -45℃, suitable for use in cold outdoor regions such as Russia, North America, and Europe .
(Note: Currently, some places with high fire protection requirements also use synthetic ester or natural ester plant-based insulating oils, but traditional “ordinary oil-based transformers” still mainly use mineral oil.)
- How much oil should be filled? (Judgment criteria)
There is no fixed amount of oil to add to a transformer; it depends on the transformer’s capacity (kVA) and dimensions, but there are two clear criteria:
- Structural Standards (Full Tank Required) : The main oil tank of the transformer must be completely filled with oil, ensuring that the core, windings, and tap changer are completely submerged below the oil level, with no air remaining.
- Oil level standard (read the scale) : When the ambient temperature is around 20℃ , the oil level gauge pointer or oil level on the oil conservator (oil tank) should be near the 1/2 mark . As the operating temperature changes, fluctuations in the oil level between 1/4 (low temperature/shutdown) and 3/4 (high temperature/full load) are normal.
- Approximate oil weight reference for common capacities
The oil weight (kg) will be clearly marked on the equipment’s nameplate. Taking a common 10kV distribution transformer as an example, the approximate oil weight is as follows:
- 100 kVA : Approximately 150 – 220 kg
- 315 kVA : Approximately 300 – 400 kg
- 630 kVA : Approximately 450 – 600 kg
- 1000 kVA : Approximately 650 – 850 kg
(Note: Different manufacturers’ corrugated tank designs or fully sealed structures can result in significant differences in oil weight. The specific filling amount must be based on the equipment nameplate markings and the actual oil level gauge reading .)
- Refueling and Maintenance Precautions
- Mixing is prohibited : Before mixing new oils of different grades (such as No. 25 and No. 45) or from different manufacturers, a mixing test must be conducted to prevent the formation of sludge that could affect heat dissipation and insulation.
- Vacuum oil filling and settling : After oil filling for new installation or major overhaul, it is necessary to let it stand for 12 to 24 hours (the higher the voltage level, the longer the settling time) until the internal air bubbles are completely expelled before powering on and putting it into operation.
If you are preparing to add oil to a transformer or select a suitable model, please let me know:
- The specific capacity (e.g., 500kVA) and model (e.g., S11, S13) of the transformer.
- Lowest temperature in the area where the equipment is located
- Is this a case of adding oil to a newly filled tank or replenishing oil during operation when it is low on oil ?
Regarding the oil used in ordinary oil-immersed transformers, besides the type and quantity, the routine oil replenishment procedures, oil aging assessment, and differences between fully sealed transformers are also crucial aspects in practical work. The following provides further explanation:
- How do I determine if a transformer needs oil replenishment or an oil change?
Transformer oil in operation will gradually deteriorate due to temperature changes and oxidation, and needs to be checked in the following three aspects:
- Observe the oil level : If the oil level gauge shows a reading below the standard mark corresponding to the ambient temperature (or even the oil level is not visible), it indicates a leak or a serious lack of oil. The leak must be located immediately and oil must be added.
- Observe the oil color : Qualified new transformer oil is light yellow, clear and transparent , without suspended matter or sediment. If the oil color turns dark brown, dark red or even black , or becomes cloudy, it indicates that the oil has been severely aged or has been exposed to moisture, and it needs to be filtered or replaced.
- Regular testing (oil chromatography and withstand voltage test) : Power regulations require regular oil sampling to test breakdown voltage (usually not less than 35kV~40kV, depending on the voltage level) and trace moisture content . If the indicators fail to meet the requirements, a vacuum oil filter must be used for degassing and dehydration treatment, or the oil must be replaced directly.
- Standard procedures for on-site oil replenishment
If it is necessary to add a small amount of insulating oil to a transformer that is in operation or out of service, the requirements for moisture and gas prevention must be strictly followed:
- Power outage and safety confirmation : When adding oil to a small distribution transformer, it is usually necessary to first shut off the power and confirm that the oil temperature has dropped to near the ambient temperature (to avoid inaccurate judgment due to hot oil expansion).
- Oil inspection and blending test : The new oil must pass the withstand voltage test and be of the same grade and oil base as the original transformer oil; if they are different, a blending test must be performed first (mix according to the actual ratio and heat and age to confirm that no sediment is precipitated).
- Injecting oil from the bottom valve : When injecting oil, it is usually pumped slowly from the oil drain valve/oil injection valve at the bottom of the transformer tank , allowing the oil level to rise steadily from bottom to top, and expelling air from the top vent plug or breather.
- the oil replenishment is completed, open the vent plug on the transformer top cover or bushing until oil flows out steadily and no more bubbles emerge, then tighten it; let it stand for several hours to confirm that there is no leakage before restoring power.
- Supplementary Notes: Fully Sealed Corrugated Tank Transformer
the corrugated oil tank transformers such as S11, S13, and S20 currently in widespread use on the market employ a fully sealed structure (eliminating the top oil conservator) .
- It has its own expansion space : it relies on the elastic deformation of the corrugated sheets around the oil tank to absorb the thermal expansion and contraction of the transformer oil. It is filled with oil and sealed in a vacuum state when it leaves the factory.
- No need for daily oil replenishment : Fully sealed oil transformers usually do not have an oil level gauge on the top (some are equipped with an oil level observation window or pressure relief valve), and do not need to be opened for oil replenishment during normal service life ; once oil shortage or oil leakage is found, it means that the box seal has failed, and a professional manufacturer is required to perform vacuuming and oil injection repair.
If you would like to know more about the details of the actual operation, please let me know:
- Is the transformer you currently have a traditional structure with an oil conservator , or a fully sealed corrugated oil tank?
- What specific situation are you facing (e.g., low oil level , discovered leak , or preparing to conduct a preventative test )?
I can outline the corresponding on-site handling steps for you.
Transformers using bio-oil (natural ester insulating oil) are primarily oil-immersed transformers with strict requirements for fire safety, environmental protection, or high overload capacity. These transformers are commonly referred to as natural ester insulating oil transformers (or vegetable oil transformers) and are widely used in densely populated areas, ecologically sensitive zones, and the new energy sector.
- Which transformers use bio-oil? (By application scenario)
Bio-oil (generally refined from vegetable oils such as soybean oil, rapeseed oil, and palm oil; common brands include FR3) is more expensive than ordinary mineral oil, but it is widely used in the following types of transformers:
- Transformers in high-fire-resistance locations , such as commercial complexes, hospitals, schools, subway stations, underground substations, high-rise buildings, and offshore wind power platforms. Bio-oil has a flash point of over 350℃ (compared to approximately 160℃ for ordinary mineral oil), classifying it as a K-grade high-flammability insulating oil. It virtually eliminates the risk of fire spread and can replace some dry-type transformers.
- Transformers in environmentally and ecologically sensitive areas : such as water source protection areas, nature reserves, farmland and forest areas, urban parks, etc. Bio-oil has a biodegradation rate of over 98% in soil or water within 28 days , is non-toxic and harmless, and will not pollute groundwater or soil even if a leak occurs.
- Transformers requiring high overload and long lifespan : such as photovoltaic power plants, wind farms (panel substations), electric vehicle supercharging stations, and industrial enterprises with large load fluctuations. Bio-oil has extremely strong water absorption properties, continuously absorbing moisture from the insulation paper, delaying insulation paper aging, and enabling the transformer to withstand higher operating temperatures (allowing a temperature rise of approximately 15-20K higher than ordinary oil-insulated transformers), achieving a 15%-20% increase in overload capacity within the same volume .
- Key Comparison Between Bio-oil Transformers and Ordinary Oil-fired Transformers (Mineral Oil)
| Comparison Dimensions | Bio-oil transformer (natural ester) | Ordinary oil becomes (mineral oil) |
| Ignition point/Flash point | Ignition point > 350℃, flash point > 300℃ (extremely difficult to ignite) | Ignition point ≈ 160℃, flash point ≈ 140℃ (flammable) |
| Environmentally friendly and biodegradable | Degradation rate > 98% in 28 days, non-toxic and environmentally friendly. | It is difficult to degrade, and leaks will seriously pollute soil and water sources. |
| Anti-aging and temperature resistance | It has strong moisture absorption and paper retention capabilities, extending insulation life by 3 to 5 times. | For standard temperature resistance grades, moisture easily accelerates the aging of insulating paper. |
| Low temperature fluidity | High pour point (approximately -15℃ to -21℃), special formulations are required in extremely cold regions. | A full range of models are available (e.g., No. 45 oil can withstand temperatures down to -45℃), with strong cold resistance. |
| Structural sealing requirements | It must be completely sealed (contact with air will cause it to oxidize, thicken, and increase its acid value). | Fully sealed or open/capsule type with oil reservoir can be used. |
| Initial procurement costs | Higher (oil prices are approximately 2 to 3 times higher than mineral oil prices) | Lower cost, mature technology, high cost performance |
- Structural characteristics and usage limitations of bio-oil transformers
- Strictly sealed design : Vegetable oil contains unsaturated fatty acids, which, if exposed to oxygen in the air for a long time, will undergo oxidation and polymerization, causing the oil to thicken or even become gel-like. Therefore, transformers using bio-oil almost all adopt a fully sealed corrugated tank structure (without conventional breather, and strictly prohibiting open contact with air).
- Limited in extremely cold regions : Natural vegetable oils have a rapid viscosity increase at low temperatures (the pour point is usually around -18℃). In outdoor environments with extreme low temperatures (below -30℃) in winter, such as Northeast and Northwest China, if a transformer is cold-started after being shut down, the oil may be too viscous and affect heat dissipation. Therefore, mineral oil No. 45 or synthetic esters are still the main choice for high-altitude outdoor areas.
If you are considering selecting or evaluating renovation options for your project, please let me know:
- The installation environment of the transformer (indoor/basement, outdoor urban area, or remote ecological area).
- Local winter minimum temperature
- The core requirements of the project (focus on fire safety , environmental compliance , or initial budget control ).
- Jiangsu Shendian Electric’s distribution transformers have a normal service life of 20 years and a 2-year warranty, making them a wise choice.