1600 kVA Oil Transformer/

1600 kVA 15 kV Oil-Immersed Step-Up Transformer for Small Wind Clusters & Remote Hydro Sites – 0.4/15 kV, Copper Wound, IEC 60076

Model:S22-M-1600/15 (S20-M-1600/15 and S13-M-1600/15 optional)

Rated Capacity:1600 kVA

Function:Generator step-up (GSU): 0.4 kV generator side → 15 kV collection side (bidirectional capability for site back-feed)

Phase / Frequency:Three-phase / 50 Hz or 60 Hz

Rated High Voltage (HV):15 kV (13.8 kV / 11 kV / 10 kV / 20 kV optional)

HV Tapping Range:±2×2.5% off-circuit (±5% or OLTC on request for weak-grid feeders)

Rated Low Voltage (LV):0.4 kV (0.415 kV / 0.69 kV on request)

Vector Group:Dyn11 standard; YNd11 optional where the utility requires a solidly earthed HV neutral

Cooling Method:ONAN standard; ONAF optional for high ambient

Winding Material:Copper — HV and LV (aluminium optional)

No-Load Loss (P0):960 W — S22 Class 1 (1,050 W S20 / 1,170 W S13), referenced to GB 20052-2024 10 kV table — 15 kV value to be confirmed by factory

Load Loss (Pk at 75 °C):10,440 W — S22 Class 1 (11,600 W S20 / 14,500 W S13), referenced to GB 20052-2024 10 kV table — 15 kV value to be confirmed by factory

  • Product Details
  • FAQs
  • Packing & Delivery

Quick Answer

A 1600 kVA 15 kV oil-immersed transformer for a small wind cluster or remote hydro site is a generator step-up (GSU) transformer that raises 400 V generator output to a 15 kV collection feeder for grid export or a long distribution line. For weak grids and remote sites, specify a hermetically sealed copper-wound unit, a low no-load loss core because the transformer stays energised around 7,000–8,760 hours a year, a harmonic-rated design to IEEE C57.110 for turbine converters, and either Dyn11 or YNd11 depending on which side needs a grounded neutral.

Product Overview

This is a three-phase, 50/60 Hz oil-immersed generator step-up transformer rated 1600 kVA, with a low-voltage winding of 0.4 kV connected to the generator bus and a high-voltage winding of 15 kV connected to the collection network. Both windings are copper. Standard vector group is Dyn11; YNd11 is supplied where the utility requires a solidly earthed HV neutral. Cooling is ONAN as standard, with ONAF available for high-ambient sites. The active part sits in a hermetically sealed corrugated-fin tank with no conservator, so the insulating oil never contacts air and needs no sampling, filtration or topping-up over the 25-year design life.

It is built for clustered and remote generation: several small wind turbines collected at one pad, run-of-river and small hydro stations, island microgrids and weak-grid sites at the end of a long feeder. The standard supply includes oil and winding temperature monitoring with alarm and trip contacts plus an RS485/Modbus RTU interface; an optional 4G or LoRa DTU publishes data to the site SCADA or a cloud dashboard, which matters when the nearest service crew is hours away. Designed and tested to IEC 60076-1/-2/-3/-5/-10, GB 1094 and GB/T 6451, with efficiency graded to GB 20052-2024. Harmonic duty is designed with reference to IEEE C57.110; grid interconnection follows IEEE 1547-2018 or IEC 61727 as required.

Why a Sealed Step-Up Transformer for Remote Wind and Hydro

Our recommendation: for an unattended wind cluster or remote hydro station, use a hermetically sealed oil-immersed step-up transformer; reserve cast resin dry type for indoor or underground installations where local fire code excludes oil. The reason is duty, not preference. Resource output is variable and often low, so the transformer spends most of its life at light load, where no-load loss dominates — a low P0 core saves more energy over 20 years than a small reduction in load loss. Oil also has far greater thermal mass than resin, which helps when wind gusts or water flow swing the load repeatedly, and a sealed tank removes the maintenance item a remote site can least afford: oil sampling, breathers and conservator checks.

Energy Efficiency Grades and 20-Year Running Cost

A step-up transformer at a renewable site stays energised even when output is low, so no-load loss runs up to 8,760 hours a year. That makes the efficiency grade worth more than the purchase price difference — especially at a remote site where every kWh may come from diesel backup or a limited feeder.

Compared with Class 3, a Class 1 unit saves about 26,000 USD in electricity over 20 years on a run-of-river hydro duty, and about 12,800 USD on a wind-cluster duty — usually several times the price difference between the two grades.

GB 20052-2024 grade Model No-load P0 Load Pk (75 °C) Annual loss – wind Annual loss – hydro 20-yr cost – wind 20-yr cost – hydro
Class 3 (NX3) S13-M-1600/15 1,170 W 14,500 W ≈ 22,683 kWh ≈ 42,613 kWh ≈ USD 54,440 ≈ USD 102,272
Class 2 (NX2) S20-M-1600/15 1,050 W 11,600 W ≈ 19,145 kWh ≈ 35,089 kWh ≈ USD 45,948 ≈ USD 84,214
Class 1 (NX1) S22-M-1600/15 960 W 10,440 W ≈ 17,362 kWh ≈ 31,712 kWh ≈ USD 41,669 ≈ USD 76,108

Grid-Connected Cluster vs Remote Island Duty

Item Grid-connected wind cluster / small hydro Remote island or weak-grid site
Power flow One-way 0.4 → 15 kV export to the utility feeder Export by day; 15 → 0.4 kV back-feed for site loads at night, or a separate auxiliary transformer
Neutral and earthing As the utility requires; YNd11 if the HV neutral must be solidly earthed LV neutral must be earthed (TN-S or TT) — Dyn11 provides it; a grounding transformer may be needed if HV is delta
Vector group YNd11 or Dyn11 per the grid code Dyn11 default, because the 400 V side feeds site loads and needs a neutral
Protection Directional overcurrent, transformer differential, anti-islanding to IEEE 1547 / IEC 61727 Same, plus load management; note converter fault current is only about 1.1–1.5 pu after a few cycles
Power quality THDv below 5% at the point of common coupling to IEEE 519-2022 Voltage and frequency set by the inverter; transformer sized on peak load and diversity
Monitoring SCADA via Modbus or IEC 61850 gateway 4G/LoRa DTU; satellite backhaul where there is no mobile coverage

Key Features

  • Step-up duty, 0.4 kV to 15 kV — a generator step-up (GSU) transformer for wind turbine clusters and small/micro hydro stations; 13.8 kV, 11 kV, 10 kV and 20 kV HV options available on request.
  • Low no-load loss for variable renewable output — S22 Class 1 at 960 W P0 versus 1,170 W for S13; at hydro duty the Class 1 unit saves roughly 26,000 USD over 20 years at USD 0.12/kWh.
  • Harmonic-capable design — K-4 / K-9 / K-13 winding design and IEEE C57.110 loading study for turbine and hydro converter harmonics (5th, 7th, 11th, 13th); an electrostatic shield between windings is available to block inverter common-mode transients.
  • Dyn11 or YNd11, chosen for the neutral — Dyn11 gives a grounded 400 V neutral for site loads and traps 3rd-order harmonics in the delta; YNd11 is supplied when the utility requires a solidly earthed 15 kV neutral.
  • Hermetically sealed corrugated tank — no conservator, no oil sampling, no breather replacement for the 25-year design life; the single most valuable feature for an unattended remote site.
  • Built for thermal cycling — ONAN cooling with high oil thermal mass, reinforced clamping and pressboard spacers for the repeated load swings of wind gusts and seasonal water flow; ONAF optional for high ambient.
  • Copper windings on HV and LV — lower load loss, lower temperature rise and better short-circuit withstand than aluminium, verified by type test to IEC 60076-5.
  • Ferroresonance and weak-grid aware — impedance and winding configuration can be specified to avoid ferroresonance with long MV cable capacitance; OLTC or a wider off-circuit tap range available for weak feeders.
  • Remote-site construction — fluororubber seals proven from -25 °C to +55 °C, high-altitude design up to 3,000–4,000 m, C4/C5-M coating for coastal or humid sites, IP54 cable boxes, anti-theft hardware and surge arresters.
  • Environmentally sensitive options — natural ester (FR3) filling and full spill containment for hydro intakes, rivers and protected areas, where mineral oil needs a bund.
  • Smart-ready — oil and winding temperature, load current and voltage via RS485/Modbus RTU, with optional 4G or LoRa DTU to the site SCADA or a cloud dashboard.

Typical Applications

  • Small wind clusters and community wind farms — several turbines collected at one 1600 kVA pad
  • Run-of-river and small hydro stations, grid-connected or islanded
  • PV + wind + battery hybrid plants sharing one 15 kV collection feeder
  • Remote villages, mines and telecom sites at the end of a weak distribution line
  • Island microgrids where the transformer sees both export and site back-feed
  • Mountain hydro sites above 1,000 m altitude with large daily temperature swing
  • Turnkey delivery inside a prefabricated substation or YBM compact substation

Standards and Certifications

Designed and tested to IEC 60076-1 (general), IEC 60076-2 (temperature rise), IEC 60076-3 (insulation levels and dielectric tests), IEC 60076-5 (short-circuit withstand) and IEC 60076-10 (sound level), plus the GB 1094 series and GB/T 6451. Energy performance is graded to GB 20052-2024, which since 2025-02-01 covers PV, wind and storage transformers in the 6–35 kV range. Harmonic duty is designed with reference to IEEE C57.110; grid interconnection follows IEEE 1547-2018 or IEC 61727, and power quality at the PCC is assessed to IEEE 519-2022. Manufactured under ISO 9001, ISO 14001 and ISO 45001. CE conformity is available on request; third-party type test reports from a CNAS-accredited laboratory (KEMA or equivalent) are available on request.

Q1: How do I size a step-up transformer for a cluster of small wind turbines?

A: Size it from the coincident electrical output, not the sum of turbine nameplates. Take each turbine’s rated kW, multiply by the cluster diversity factor (typically 0.8–0.9 for wind because turbines do not all see the same wind speed), divide by power factor, then add 10–20% for site loads and future turbines. A 1600 kVA unit typically collects roughly 1.2–1.8 MW of small turbines depending on the turbine mix and load factor. Confirm the generator output voltage — this unit is supplied with a 0.4 kV LV winding, and 0.69 kV is available on request.

Q2: Dyn11 or YNd11 — which vector group should a generator step-up transformer use?

A: It depends on which side needs a grounded neutral. Dyn11 puts the delta on the 15 kV side and a grounded star on the 400 V side, which suits a site where the LV bus also feeds lighting, auxiliaries and other 400 V loads; the delta also circulates 3rd-order harmonics. YNd11 puts a grounded star on the HV side and a delta on the generator side, and is specified when the utility requires the 15 kV neutral to be solidly earthed or when the generator manufacturer requires a delta connection. Confirm the utility and generator requirements before ordering — this is the single most common specification error on GSU transformers.

Q3: Why use 15 kV instead of 10 kV for a remote wind or hydro site?

A: 15 kV is a common collection and distribution voltage in export projects and North American 15 kV class systems. For the same power, a higher voltage means lower current, smaller conductor cross-section and lower I²R loss over a long line — which is exactly the constraint at a remote hydro intake or a wind cluster spread over several kilometres. If the local utility feeder is 10 kV, 11 kV or 20 kV, the same transformer can be built to that voltage; the loss values then follow the corresponding GB table.

Q4: Does a wind or hydro step-up transformer need a K-rating?

A: Usually yes in practice. Wind turbine full-scale converters and variable-speed hydro inverters inject 5th, 7th, 11th and 13th harmonic currents, which increase winding eddy loss and hot-spot temperature beyond what the nameplate kVA implies. Specify K-4 for modest converter duty and K-9 or K-13 for dense converter loading, and ask for an IEEE C57.110 loading study. K-rating protects the transformer; it does not clean up the upstream supply, so active filtering may still be needed to meet IEEE 519 at the point of common coupling.

Q5: How much energy does a 1600 kVA transformer lose when the wind or water is low?

A: No-load loss continues whenever the transformer is energised, so it dominates at low output. On GB 20052-2024 values, S22 Class 1 loses 960 W no-load against 1,170 W for S13 Class 3. Over 20 years at USD 0.12/kWh that is roughly USD 26,000 less cost on a run-of-river hydro duty and about USD 12,800 less on a wind-cluster duty. Ask for the site capacity factor and electricity price and we will recalculate — that is the number that decides the grade.

Q6: Can the transformer handle reverse power flow for site loads?

A: Yes. The windings and core have no directional limit, so a 15 → 0.4 kV back-feed works electrically. What must be designed for is protection and voltage control: converter-based generators contribute limited fault current (roughly 1.1–1.5 per unit after a few cycles), so directional overcurrent and anti-islanding settings need coordination to IEEE 1547-2018 or IEC 61727. Where back-feed is continuous, a separate auxiliary transformer is often cleaner.

Q7: What causes ferroresonance on long medium-voltage cables, and how is it avoided?

A: Ferroresonance occurs when the magnetising reactance of an unloaded transformer resonates with the capacitance of a long MV cable, typically during single-pole switching or a fault on one phase. Voltage can rise to dangerous levels. It is avoided by choosing the winding configuration and impedance for the actual cable length, by avoiding single-pole switching where possible, and by adding damping or a grounding transformer where the system is ungrounded. Tell us the cable length and earthing arrangement at enquiry stage and we will review it.

Q8: Is an oil-immersed transformer acceptable at an environmentally sensitive hydro site?

A: Yes, with the right specification. A hermetically sealed corrugated tank has no conservator and no routine oil handling, so the main risk is a leak rather than routine maintenance. Where the site sits near a water intake, river or protected area, specify natural ester (FR3) filling and a bund or spill-containment tray. Ester oil is biodegradable and has a much higher fire point than mineral oil. Where local fire code forbids combustible oil indoors, use cast resin dry type instead.

Q9: Can it run at high altitude and at -40 °C?

A: Standard design covers up to 1,000 m and -25 °C to +40 °C. Mountain hydro sites often need a high-altitude design up to 3,000–4,000 m with increased clearances and derating, and cold-climate sites need low-temperature oil, a heater and different gasket compound for -40 °C. State altitude and minimum ambient temperature in the enquiry so the insulation and oil are selected correctly.

Q10: What is the typical delivery time, packing and standards documentation?

A: Production is typically 4–8 weeks for a 1600 kVA 15 kV unit, depending on specification and quantity. Units ship oil-filled and sealed on a steel-reinforced pallet, wrapped in moisture-barrier film with desiccant, with bushings and cable boxes guarded by plywood, lifting lugs and shock/tilt indicators; full export crating is available. Documents supplied include the IEC 60076 routine and type test reports, GB 20052-2024 efficiency calculation, outline drawing and packing list. CE conformity is available on request. UL 1562 listing is not currently held — please tell us if your project requires it.

Shipped oil-filled and factory-sealed on a steel-reinforced wooden pallet, wrapped in moisture-barrier film with desiccant, HV and LV bushings plus cable boxes protected by plywood guards, fitted with lifting lugs and shock/tilt indicators. Suitable for sea, road and rail transport to landlocked sites; full export plywood crate available on request. Where destination regulations require, the unit can be shipped drained with oil in sealed drums. For high-altitude or cold-climate sites, oil and accessories are packed separately with anti-freeze protection. Final gross weight, crate dimensions and packing list confirmed before shipment.